청정 순환 냉각탑의 집수 출구에 스테인레스 스틸 필터를 설치하십시오.
1. 문제
청정 재순환수 시스템에는 처리 용량이 700m3/h인 3개의 포장형 냉각탑이 있으며, 이는 간접 냉각수를 냉각하기 위해 지속적으로 작동하므로 간접 냉각수 공급의 수온은 다음과 같습니다.<30℃ to meet the needs of users. Cooling medium corrugated packing for cooling towers in clean ring systems. The Indirect cooling water continuously disperses into water droplets from top to bottom along the plastic corrugated filler, increasing the contact area with the air and cooling down. During the long-term process of water droplets eroding the plastic corrugated filler, the plastic corrugated filler will be partially broken and enter the clean recirculating water, and flow into the clean recirculating water pool with the water. If the filler is sucked into the pump body, pipeline filters, and various user equipment and pipelines by the clean recirculating wate supply pump, it may cause damage to the equipment, blockage of pipeline nozzles, etc.
2. 변환 조치
3개의 네트링 FRP 냉각탑 사각 집수구에 스테인레스 스틸 필터를 설치하여 파손된 충진재를 차단하고 장비 및 배관 내부로 유입되는 것을 방지합니다. 필터 3세트. 제작 방법은 다음과 같습니다. 한 변의 길이가 1m이고 구멍 직경이 10mm×10mm인 사각 스테인레스 스틸 필터를 절단합니다. 파이프용 구멍을 확보하기 위해 필터 중앙에 직경 400의 구멍을 잘라냅니다. 그런 다음 정사각형 필터의 네 측면에 평강을 용접하고 나사로 평강에 필터 스크린을 고정합니다. 스테인레스 스틸 필터 스크린을 경사진 가장자리와 사각형의 중앙에 묶어 내식성을 강화합니다. 마지막으로 개스킷을 2개로 절단하고 양쪽을 용접하여 고정나사로 연결하여 설치가 용이합니다. 제작 후 설치가 매우 쉽습니다. 설치 과정에서 간접 냉각수는 냉각탑으로 올라가는 대신 일시적으로 우회 배관을 통해 전달됩니다. 사람들은 냉각탑 안으로 들어가 만들어진 필터 두 개를 닫는다. 고정 나사를 통해 정사각형으로 접합되고 중앙에는 DN400 나사산이 있습니다. 수도관 필터. 설치에는 20분이 소요되며, 우회관을 닫아 냉각탑에 물을 공급하므로 기본적으로 일반 생산 시 냉각탑 사용에는 영향을 미치지 않습니다.
3.수정 효과
냉각탑의 플라스틱 골판형 필러에 의해 냉각된 깨끗한 재순환수는 스테인레스 스틸 필터로 여과된 후 냉수 풀로 흘러야 합니다. 깨진 플라스틱 필러는 필터에 의해 차단됩니다. 작업자는 검사를 통해 관찰하고 교대 근무 중 짧은 생산 중단 시간을 활용합니다. 바이패스 밸브를 열고 냉각탑으로 들어가 필터에 걸러진 필러와 쓰레기를 청소할 수 있습니다. 이 방법은 구성이 상대적으로 간단하고 일상적인 운영이 간단하지만 청정 순환수 시스템 장비 전체의 안전한 생산을 보호하는 데 있어 매우 효과적이며 장기적인 역할을 합니다.

 

1 5

 

2 6

 

2 7

 

2 27